Ingeteam 160TL Installation And Operation Manual page 94

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 61
Ingeteam
Each individual string must not exceed 20 Adc.
CAUTION
The strings connected to the unit's connectors must be electrically independent of each other. That is, there
must not be any strings with a current higher than that permitted separated into several connectors, as the
current distribution is never guaranteed.
The cabling used for the connection must have dimensions in line with current regulations in the country of
installation and according to the type of installation, connectors, and maximum current and voltage of the PV array.
The unit includes fuses in the PV+ inputs. If it is necessary to mount fuses on the PV inputs- these can be
mounted externally using standard references for the Sunclix family by Phoenix Contact.
The table below shows the recommended fuses by maximum string current together with the Phoenix Contact
references:
Maximum string power Impp
9 A
11 A
13 A
15 A
18 A
20 A
94
PV fuse-
Fuses recommended for PV-
Fuse
15 A
20 A
25 A
32 A
Phoenix Contact fuse reference
PV-PRO/M/F-200/F-1500/13
PV-PRO/M/F-200/F-1500/17
PV-PRO/M/F-200/F-1500/20
PV-PRO/M/F-200/F-1500/25
ABZ2011IQM01_F - Installation and Operation Manual
DC connection

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ingecon sun 3play

Table of Contents