Process data description
The process data are generated from CoE objects 0x6000 [} 158] (inputs) and 0x7000 [} 159]
(outputs).
5.7.1

Restore object

Index 1011 Restore default parameters
Index
Name
(hex)
1011:0
Restore default
parameters [} 184]
1011:01
SubIndex 001
5.7.2

Configuration data

Index 8000 SAI Settings
Index (hex) Name
8000:0
SAI Settings
8000:01
Enable vendor
calibration [} 157]
8000:02
Enable user calibration
[} 155]
8000:04
Enable filter [} 145]
8000:09
Disable autorange
[} 145]**
8000:0A
Frequency** [} 145]
8000:0D
Mode [} 144]**
8000:11
Range [} 145]**
8000:19
Zero compensation
interval [} 146]
8000:1D
Presentation [} 146]
**) Selection of the measuring range via CoE requires SAI Range (Outputs) PDO 0x1600 [} 160] to be
switched off. If SAI Range (Outputs) PDO is activated, the CoE entries are based on the range used. In this
case writing of the CoE entries "Disable autorange", "Mode" and "Range" is disabled.
Index 8002 SAI User data
The "User data" index contains an Offset/Gain pair of values for each measuring range, in order to enable
user calibration for each range. User calibration is switched on and off for all measuring ranges via index
0x8000:02 [} 155] "Enable user calibration".
The default values are 0x0000 for offset and 0x2000 for gain (see Calibration section). The default settings
can be restored via the entry 0x1011 [} 155] "Restore default parameters".
EL3681
Meaning
Restore default parameters
If this object is set to "0x64616F6C" in the set value
dialog, all backup objects are reset to their delivery state.
Meaning
Maximum subindex
Enabling of the vendor calibration
Enabling of the user calibration
Enable filter, this reduces the number of new
measured values
The automatic measuring range selection is disabled
Selection of the mains frequency (50/60 Hz)
The measurement mode in which the next
measurement is to take place.
The measuring range in which the next measurement
is to take place
Time interval between the measurements of the
internal ADC offset and activation of the offset
Selection of the presentation: left/right-justified, scaled
(e.g. 1 bit/µV)
Version: 3.0
Commissioning
Data type
Flags Default
UINT8
RO
0x01 (1
UINT32
RW
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x1D (29
BOOLEAN
RW
0x01 (1
BOOLEAN
RW
0x00 (0
BOOLEAN
RW
0x01 (1
BOOLEAN
RW
0x00 (0
BIT1
RW
0x00 (0
BIT4
RW
0x00 (0
UINT8
RW
0x00 (0
BIT4
RW
0x00 (0
BIT4
RW
0x02 (2
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
155