Technical Data - Beckhoff EL3681 Documentation

Digital multimeter terminal
Table of Contents

Advertisement

2.2

Technical data

Technical data
Number of inputs
Technology
Measured values
Measuring ranges voltage
Dielectric strength - Destruction limit
Measuring ranges current
Current resistance - destruction limit
Measuring procedure
Resolution
Sampling type
Ground reference
Internal resistance
Measuring error
Update time
Electrical isolation
Supply voltage for electronic
Current consumption via E-bus
Configuration
Weight
Permissible ambient temperature range during
operation
Permissible ambient temperature range during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 38]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Calibration certificate
*)
Marking
*) Real applicable approvals/markings see type plate on the side (product marking).
*) In AC mode, the terminal operates in TrueRMS mode, i.e. it does not digitally record the peak values Vpp,
which are approx. 1.4 times larger, but the RMS value, see "Measuring procedure [} 21]" and chapter
"Technology [} 20]".
EL3681
EL3681
EL3681-0020
1, voltage or current (1 A / 10 A)
digital multimeter with automatic range selection
Current AC/DC, Voltage AC/DC
300 mV, 3 V, 30 V, 300 V
480 V AC
DC
RMS/
100 mA, 1 A and 10 A via high-current path
Measuring range 1 A: given by fuse;
Measuring range 10 A: short-time withstand current 30 A for 1 sec (min.
5 min. cooling time)
AC with TrueRMS value generation, 0..1 kHz input signal, crest factor < 3
permitted
18 bit + sign in each measurement range
simultaneous
differential
Measuring range DC 300 mV – 300 V: 12.5 MΩ
Measuring range DC 100 mA – 1 A: 0.2 Ω
Measuring range DC 10 A: 3 mΩ
Measuring range AC 300 mV - 300 V: 1 MΩ, approx. 33 pF
Measuring range AC 100 mA – 1 A: 0.2  Ω
Measuring range AC 10 A: 3 mΩ
see table [} 21] in chapter "Accuracy"
0.5 s, 1 s for measuring range selection
1,500 V (connection terminal/E-bus)
via the E-bus
typ. 150 mA
via TwinCAT System Manager
approx. 70 g
-25 °C ... +60 °C
0 °C ... +55 °C
(extended temperature
range)
-40 °C ... +85 °C
-25 °C ... +85 °C
95 %, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
-
with factory calibration
certificate [} 23]
CE, EAC, UKCA
Version: 3.0
Product description
EL3681-0030
**)
with external calibration
certificate [} 23]
19