Installing The Intrusion Switch Module - Dell PowerEdge XR7620 Installation And Service Manual

Table of Contents

Advertisement

3.
Remove the 2U air
shroud.
NOTE:
Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
NOTE:
The procedure to remove the intrusion switch module is the same for Rear Accessed and Front Accessed
configurations.
Steps
1. Disconnect the intrusion switch cable from the connector on the system board.
2. Using a Phillips #1 screwdriver, loosen the screw on the intrusion switch module.
3. Slide the intrusion switch module out of the slot on the system.
NOTE:
The numbers on the image do not depict the exact steps. The numbers are for representation of sequence.
Figure 147. Removing the intrusion switch module
Next steps
1.
Replace the intrusion switch

Installing the intrusion switch module

Prerequisites
1. Follow the safety guidelines listed in the
2. Follow the procedure listed in the
3.
Remove the 2U air
shroud.
NOTE:
Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
NOTE:
The procedure to install the intrusion switch module is the same for Rear Accessed and Front Accessed
configurations.
Steps
1. Align and slide the intrusion switch module into the slot in the system until firmly seated.
2. Using a Phillips #1 screwdriver, tighten the screw on the intrusion switch module.
3. Connect the intrusion switch cable to the connector on the system board.
172
Installing and removing system components
module.
Safety
instructions.
Before working inside your
system.