How hysteresis affects the output on/off points when if the sensor is configured with mode = Swtch_|- and SPtRef configured
Press the up button to manually select a constant hysteresis value between 2 mm and 12000 mm. 
Navigate: MENU › D_OUT › Hyst 
Remote Input: Not available 
Default: Auto 

Timer

The Timer option sets the delays and timers. On/Off Delays and On/Off One-Shot timers can be programmed between 1 to
9999 ms (a value of 0 disables the delay/timer). The following figure defines how the delays/timers affect the output behavior. 
  Navigate: MENU › Dx_OUT › Timer 
Remote Input: not available 
Default: 0 ms for all timers 
Output
OFF Delay
OFF 1-Shot
D
ON Delay
D
ON 1-Shot
Some combinations of delays/timers are not allowed. The programming menu automatically disables invalid combinations of delays/timers. The following ta-
ble shows the allowable combinations of delays/timers. 
 Off Delay (OffDly) 
 
 
26
Setpoint Mode Example:
Far
Near
On
Off
D
D
D
D
Time
Off Delay 
OK 
© Banner Engineering Corp.
as Backgrnd
Mode = Swtch
SPtRef = Backgrnd
Delays/Timers
ON
OFF
D
D
(D = 1 - 9999 ms)
Off One-Shot Timer 
OK 
OK 
Continued on page 27
Setpoint
Hysteresis
Signal
Output
On Delay 
On One-Shot Timer 
N/A 
June 22, 2023
 