Do you have a question about the FC 302 and is the answer not in the manual?
Questions and answers
Ishtiaq Ahmed
March 14, 2025
Alarm-88 description required & remedy?
1 comments:
Mr. Anderson
May 14, 2025
Description: Alarm 88 on the Danfoss FC 302 indicates "Option Detection." It occurs when a change in the option layout is detected while Parameter 14-89 (Option Detection) is set to [0] Frozen configuration.
Remedy: 1. Enable option layout changes by setting Parameter 14-89 to allow changes. 2. Alternatively, restore the correct option configuration.
Need help?
Do you have a question about the FC 302 and is the answer not in the manual?
Questions and answers
Alarm-88 description required & remedy?
Description: Alarm 88 on the Danfoss FC 302 indicates "Option Detection." It occurs when a change in the option layout is detected while Parameter 14-89 (Option Detection) is set to [0] Frozen configuration.
Remedy:
1. Enable option layout changes by setting Parameter 14-89 to allow changes.
2. Alternatively, restore the correct option configuration.
This answer is automatically generated