Specifications
Specifications
For more information on cable, power, environmental, compliance, and general specifications, see the HPE Compute Transceiver and
Cable Hardware Matrix.
Cable Hardware Matrix
Environmental specifications
Environmental specifications
Specification
Specification
1
Temperature range
Temperature range
Operating
Nonoperating
Relative humidity (noncondensing)
Relative humidity (noncondensing)
Operating
Nonoperating
Altitude
Altitude
Operating
Non-operating
1
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1,000 ft) to 3,050 m (10,000 ft) is
applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change
might be limited by the type and number of options installed.
Value
Value
—
10°C to 35°C (50°F to 95°F)
-30°C to 60°C (-22°F to 140°F)
—
8% to 90%. 28°C (82.4°F), maximum wet bulb temperature
5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature
—
3050 m (10,000 ft). This value may be limited by the type and
number of options installed. Maximum allowable altitude change
rate is 457 m/min (1500 ft/min).
9144 m (30,000 ft). Maximum allowable altitude change is 457
m/min (1500 ft/min).
HPE Apollo 4200 Gen10 Plus Server Maintenance and Service Guide
HPE Compute Transceiver and
72