For more information about the specifications of power supplies, see the power supply manuals for
them.

Fan modules

The fan modules are hot swappable and supports N+1 redundancy.
The server must be fully configured with fan modules of the same model.
The server supports both single-rotor FAN-8038-2U-G6 fan module and dual-rotor FAN-8056-2U-G6
fan module. When any of the following conditions are met, you must install the FAN-8056-2U-G6 fan
module:
The 12LFF drive backplane, 25SFF drive backplane, two 8SFF UniBay drive backplanes, or
three 8SFF UniBay drive backplanes are installed along with processors with a TDP of more
than 230 W are all installed.
The processors with a TDP of more than 200 W are installed and drives are installed at the
server rear.
The A2, A30, A40, A100, or A16 GPU modules are installed.
The mid GPU module is installed.
The MBF2H332A-AENOT network adapter is installed.
55