Set The Control Panel; Set Current (Amp.) Intensity Value - Xylem Bell & Gossett GF60 Instruction Manual

Glycol make-up unit
Table of Contents

Advertisement

4 Operation
5. Adjust Cut in / cut out pressure at the control panel display.
6. Switch to mode 3 for Auto mode at control box.
Note: At Dry run condition the unit displays Off on the control panel and no operation will
carry out.
For dry run condition, switch to refilling mode and then to standard mode.
Refilling mode
1. Make sure drain valve is closed.
2. Keep delivery valve at this position looking from top.
3. Verify plumbing connections at the automatic refilling port.
4. Change control box mode to Refill and press
5. Keep refilling valve at this position looking from back.
6. Switch to mode 1 Refill mode at control box.
Note: Once the tank is full the high level switch will activate and the Red LED displays on the
control box.

4.2 Set the control panel

4.2.1 Set Current (Amp.) intensity value

1. Start pressure setting digital display by pressing
2. Press
3. LED A flashes and display will be flashing
4. Set the adjusted rated current by pressing
5. Press
Factory set to 5 amps.
10
for three seconds.
for validation.
on the pressure setting digital display.
.
and
buttons.
GF60 INSTRUCTION MANUAL