Figure 8-8: Situation #1 Diagram
A. Full tank
B. Measured at the transmitter
Solution to situation #1
Table 8-22
function block configuration.
Table 8-22: Analog Input Function Diagram for a Pressure Transmitter Used in Level
Measurement (Situation #1)
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
Rosemount OCX8800C
lists the appropriate configuration settings, and
F
Figure 8-9
illustrates the correct
Configured values
Indirect
0 to 7 psi (0 to 0.5 BarG)
0 to 16 ft (0 to 4.9 m)
Fieldbus
OUNDATION
April 2023
135