5.12 CoE

5.12.1

Most important CoE entries

Table of contents
Objects for commissioning [} 165]
Objects for the user calibration [} 166]
This chapter describes the CoE objects required for commissioning and user calibration.
Parameterization via the CoE list (CAN over EtherCAT)
The terminal is parameterized via the CoE - Online tab (double-click on the respective object) or via
the Process Data tab (allocation of PDOs). Please note the following general CoE information when
using/manipulating the CoE parameters:
- Keep a startup list if components have to be replaced
- Differentiation between online/offline dictionary, existence of current XML description
- use "CoE reload" for resetting changes
Objects for commissioning
Index 1011 Restore default parameters
Index (hex) Name
1011:0
Restore default
parameters
1011:01
SubIndex 001
EL3692
Meaning
Restore default parameters
If this object is set to "0x64616F6C" in the set value
dialog, all backup objects are reset to their delivery
state.
Version: 3.1
Commissioning
Data type
Flags
Default
UINT8
RO
0x01 (1
UINT32
RW
0x00000000
(0
dez
)
dez
)
165