Beckhoff EL3692 Manual page 112

2 channel resistance measurement terminal, high-precision
Hide thumbs Also See for EL3692:
Table of Contents

Advertisement

Commissioning
State Machine
Init
Pre-Op
Op
Bootstrap
Safe-Op
Clear Error
Current State
Requested State
DLL Status
Indicates the DLL status (data link layer status) of the individual ports of the EtherCAT slave. The DLL status
can have four different states:
Status
No Carrier / Open
No Carrier / Closed
Carrier / Open
Carrier / Closed
File Access over EtherCAT
Download
Upload
"DC" tab (Distributed Clocks)
Fig. 128: "DC" tab (Distributed Clocks)
Operation Mode
Advanced Settings... Advanced settings for readjustment of the real time determinant TwinCAT-clock
Detailed information to Distributed Clocks is specified on http://infosys.beckhoff.com:
Fieldbus Components → EtherCAT Terminals → EtherCAT System documentation → EtherCAT basics →
Distributed Clocks
112
This button attempts to set the EtherCAT device to the Init state.
This button attempts to set the EtherCAT device to the pre-operational state.
This button attempts to set the EtherCAT device to the operational state.
This button attempts to set the EtherCAT device to the Bootstrap state.
This button attempts to set the EtherCAT device to the safe-operational state.
This button attempts to delete the fault display. If an EtherCAT slave fails during
change of state it sets an error flag.
Example: An EtherCAT slave is in PREOP state (pre-operational). The master now
requests the SAFEOP state (safe-operational). If the slave fails during change of
state it sets the error flag. The current state is now displayed as ERR PREOP.
When the Clear Error button is pressed the error flag is cleared, and the current
state is displayed as PREOP again.
Indicates the current state of the EtherCAT device.
Indicates the state requested for the EtherCAT device.
Description
No carrier signal is available at the port, but the port is open.
No carrier signal is available at the port, and the port is closed.
A carrier signal is available at the port, and the port is open.
A carrier signal is available at the port, but the port is closed.
With this button a file can be written to the EtherCAT device.
With this button a file can be read from the EtherCAT device.
Options (optional):
• FreeRun
• SM-Synchron
• DC-Synchron (Input based)
• DC-Synchron
Version: 3.1