Commissioning
5.6.10
Error Codes
The terminal reports its status through various bits in the status word. The possible combinations are listed
and explained in the following table.
Er-
Under-
Over-
ror
range
range
1
1
0
1
0
1
1
0
0
1
0
0
1
0
0
0
0
0
1
0
0
Table 3: Error Codes
148
Data
Tx-
Range
Er-
in-
PDO
in-
ror
valid
State
valid
LED
0
0
0
off
0
0
0
on
0
0
0
off
0
1
0
off
0
0
1
off
1
0
0
off
1
1
0
off
Version: 3.1
Error de-
Remedy/Error
scription
Measurement
If possible use a smaller
is below range
measuring range; otherwise
increase the input signal
Measuring
If possible use a larger
range
measuring range; otherwise
exceeded
reduce the input value
Display error
Select a suitable presentation
Conversion
None (ADC does not respond,
error
automatic restart)
Measuring
Select valid measuring range;
range invalid
with Autorange perhaps select
Presentation: Scaled or activate
SAI range (outputs)
Data invalid
Request conversion (after switch
from continuous to single shot);
ensure that measuring range is
known
Conversion
None; switch on again
error after
switching on
EL3692