Setup Menu - Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION

2.5 SETUP Menu

The Setup menu (Table 2-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the Setup menu is also used to enter date and time, and units of
temperature measurements. A view-only software version display is also provided to indicate
the current C-More Controller software version.
TABLE 2-3: SETUP Menu
MENU ITEM DISPLAY
1
Password
2
Language
3
Time
4
Date
5
Unit of Temp
6
Comm Address
7
Baud Rate
8
onAER Mode
9
Min Upload Timer
10
Unit Alpha
11
Unit Year
12
Unit Serial #
13
Software
OMM-0118_B • GF-203 • 5/9/2019
AVAILABLE CHOICES OR LIMITS
Minimum
Maximum
0
English
12:00 am
11:59 pm
01/01/00
12/31/99
Fahrenheit or Celsius
0
2400, 4800, 9600, 19.2K
Ethernet or SD Card
0
9,999 Sec
E, G, H, R, N or A
0
0
Ver 0.00
Ver 9.99
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DEFAULT
9999
English
Fahrenheit
127
9600
Ethernet
99
9999
Current software
version
0
0
0
A
0
0
Page 20 of 148