Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
Temperature Channel Offset:
Items 43 – 48 embody the feature, which allow the user to field calibrate all six temperature
channels by entering an offset corresponding to the desired temperature channel.
– FFWD Temp Offset
43
– Exhst Tmp Ofset
44
– Outdr Air Offset
45
– Inlet Air Offset
46
– Inlet Wtr Offset
47
– Outlet Wtr Offset
48
49
24 hr Max Cycles
50
24 hr Max Ovrtemp
51
0-10v Out Test
52
Spark Monitor
53
Min Spark Amps
54
Max Spark Amps
OMM-0118_B • GF-203 • 5/9/2019
Range: -20 to + 20 (either ºF or °C)
Range: -20 to + 20 (either ºF or °C)
Range: -20 to + 20 (either ºF or °C)
Range: -20 to + 20 (either ºF or °C)
Range: -20 to + 20 (either ºF or °C)
Range: -20 to + 20 (either ºF or °C)
Maximum cycles in 24 hour period.
Maximum over-temp in 24 hour period.
Set the blower voltage at 0-10v for testing.
Enables or disables the Spark Monitor function, which displays the
AC current on the input of the Ignition Transformer.
Allows the adjustment of the minimum spark current required at the
spark transformer input.
Allows the adjustment of the maximum spark current required at
the spark transformer input.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 101 of 148