Setup Menu; Configuration Menu - Watts Aerco BENCHMARK 750 User Manual

Gas-fired boilers
Hide thumbs Also See for Aerco BENCHMARK 750:
Table of Contents

Advertisement

Benchmark 750 – 1000 Boiler User Manual - INTERNATIONAL

3.5 SETUP MENU

The Setup menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the Setup menu is also used to enter date and time, and units of
temperature measurements. A view-only software version display is also provided to indicate
the current Control Box software version.
Menu Item Display
1
Password
2
Language
3
Time
4
Date
5
Unit of Temp
6
Comm Address
7
Baud Rate
8
OnAER Mode
9
Min Upload Timer
10
Unit Alpha
11
Unit Year
12
Unit Serial #
13
Software

3.6 CONFIGURATION MENU

The Configuration menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the CONSTANT SETPOINT mode. The remaining options in this menu require the
valid password to be entered, prior to changing existing entries. This menu contains a number
of other configuration settings which may or may not be displayed, depending on the current
operating mode setting.
The Configuration menu settings shown in Table 3-4 are Factory-
Set in accordance with the requirements specified for each
individual order. Therefore, under normal operating conditions, no
changes will be required.
Page 42 of 170
11/03/2016
CHAPTER 3 – OPERATION
Table 3-3: Setup Menu
Available Choices or Limits
Minimum
0
English
12:00 am
01/01/00
Fahrenheit or Celsius
0
2400, 4800, 9600, 19.2K
Ethernet or SD Card
0
E, G, H, R, N or A
0
0
Ver 0.00
NOTE
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Maximum
9999
11:59 pm
12/31/99
Fahrenheit
127
9,999 Sec
99
9999
Ver 9.99
Current software version
Default
0
English
0
9600
Ethernet
0
A
0
0
OMM-0119_0A
GF-130-I