Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual page 25

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
TABLE 2-7: BST Menu
MENU ITEM DISPLAY
16
Mdbus Temp Units
17
Header Temp Addr
18
Header Temp Point
19
BST Outdoor Sens
20
Outdr Tmp Source
21
Outdoor Tmp Addr
22
Outdoor Tmp Pnt
23
BST Auto Mstr
24
BST Auto Timer
25
Remote Intlk Use
26
One Boiler Mode
27
1 Blr Threshold
28
Setpoint Setback
29
Setback Setpoint
30
Setback Start
31
Setback End
32
Rate Threshold
33
*OPERATE MENU*
34
BST Next On VP
35
BST Max Boilers
36
BST On Delay
37
BST On Timeout
38
Valve Override
39
Valve Off Delay
40
BST Sequencing
41
Select Lead Unit
42
Select Lag Unit
43
Lead/Lag Hours
44
*TEMP CTRL MENU*
45
BST Temp Hi Limit
46
BST Setpt Lo Limit
OMM-0118_B • GF-203 • 5/9/2019
AVAILABLE CHOICES OR LIMITS
Minimum
Degrees C or Degrees F
0
0
Disabled
Outdoor Temp
0
0
NOTE! A Modbus
temperature
No
transmitter must be
installed in
conjunction with this
feature.
10 sec
Boiler Shutdown
On-Outlet
Off
Temp
10
Disable
BST Setpt Lo Limit
12:00am
12:00am
1°F (0.55°C)
Disabled
16%
1
30 sec
15 sec
Off
Closed
0
Run Hours
Unit Size
0
0
25 hours
Disabled
40°F (4.4°C)
40°F (4.4°C)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Maximum
255
255
Enabled
Network
255
255
Yes
120 sec
System Shutdown
On-Avg
Temp
35
Enable
BST Setpt HI Limit
11:59pm
11:59pm
30°F (16.5°C)
Enabled
100%
8
300 sec
300 sec
Open
15 min
Select Lead
127
127
225 hours
Enabled
210°F (98.9°C)
BST Setpt HI Limit
DEFAULT
Degrees C
240
14
Disabled
Outdoor Temp
240
215
No
30 sec
System Shutdown
Off
25
Disable
130°F (54.4°C)
12.00am
12.00am
15°F (8.25°C)
Disabled
50%
8
60 sec
60 Sec
Off
1 min
Run Hours
0
0
72 hours
Disabled
210°F (98.9°C)
60°F (15.5°C)
Page 25 of 148