APPENDIX A: BOILER MENU DESCRIPTIONS
23
PWM In Adj
24
Analog In Adj
25
Flow In Adj
Supply Gas Pressure
26
In Adj
27
Gas Plate dp In Adj
28
mA Out Adj
29
A/F Sensitivity
30
Power Reset
31
Water Temp Reset
32
Gas Press Reset
33
Min Off Time
34
Stop Level
35
Start Level
SKIP FEATURE:
Items 36 – 38 embody a feature that allows the user to define a Fire Zone the C-More will avoid. In
the rare instance when a unit emits an objectionable noise at a certain Fire Rate and no other
remedy solves the problem, a Fire Rate skip zone may be defined to command the C-More to Skip-
Over the defined Fire Rate.
– Skip Range CNTR
36
– Skip Range Span
37
– Skip Speed
38
O2 Settings:
Items 39 – 41 allow calibration of oxygen readings.
– O2 Gain
39
– O2 Offset
40
– O2 Sensor
41
42
Cal Temp Sensors
OMM-0118_B • GF-203 • 5/9/2019
Allows the Pulse Width Modulation (PWM) duty cycle to be
adjusted from -5.0% to +5.0% in 0.1% increments.
Allows adjustment of the analog input from -5.0% to +5.0%.
Allows adjustment of the water Flow Rate Input from
-5.0% to +5.0%.
Allows adjustment of the Supply Gas Pressure level from
-5.0% to +5.0% in 0.1 % increments.
Allows adjustment of the Gas Plate dp level from -5.0% to +5.0% in
0.1% increments.
Allows adjustment of the milliamp output from -5.0 mA to +5.0 mA.
Allows adjustment of the Air/Fuel (A/F) Valve stepper motor
sensitivity to be adjusted from 1% to 5% in 1% increments.
Allows the Power Reset Option to be set to AUTO or MANUAL.
Allows the Water Temperature Reset function to be set to AUTO or
MANUAL.
Allows the Gas Pressure Reset function to be set to AUTO or
MANUAL.
Allows the minimum Off time to be set from 0 to 10 minutes.
Allows the Stop Level to be set to a valve position ranging from 0%
to the presently set Start Level.
Allows the Start Level to be set to a valve position ranging from the
presently set Stop Level to a maximum of 40%.
Defines the Center (Fire Rate) of the skip band.
Defines the + and – band of the Skip Zone Size.
Defines the speed (Seconds/Fire Rate) at which the band will be
skipped.
Range = 0.5 to 1.5. (Unity Gain, No Mods)
Range = -3.0 to +3.0.
Enables the O2 Sensor
Allows calibration of the temperature sensor
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 100 of 148