SECTION 5 – TROUBLESHOOTING GUIDE
TABLE 5-1: Boiler Troubleshooting Procedures
FAULT
INDICATION
7. Pilot View Port is blocked.
8. Carbon or other debris on Burner.
FLAME LOSS
DURING IGN
9. Pilot gas valve is closed.
(continued)
10. Pilot ignition solenoid valve does not open.
11. Clogged Pilot ignition piece
Worn Flame Detector or cracked ceramic.
1.
Defective Regulator.
2.
FLAME LOSS
3.
Poor combustion calibration.
DURING RUN
4.
Debris on burner.
Blocked condensate drain.
5.
6. Main Flame Detector is touching burner mesh.
1.
The Heat Demand Relays on the
Ignition/Stepper (IGST) board failed to activate
HEAT DEMAND
when commanded.
FAILURE
Relay is activated when not in Demand.
2.
Poor combustion calibration.
1.
HIGH EXHAUST
TEMPERATURE
2.
Carboned heat exchanger due to incorrect
combustion calibration.
OMM-0118_B • GF-203 • 5/9/2019
PROBABLE CAUSES
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
CORRECTIVE ACTION
7. Remove ad clean Pilot View Port. Also, ensure that the hole in the
refractory is clear.
8. Remove View-Port and inspect Burner with Boroscope. If it is fouled
or black with soot, remove the Burner and inspect for any carbon
build-up or debris. Clean and reinstall.
9. Open the Pilot gas valve on the upstream side of the SSOV (see
Figure 5-1).
10. When unit goes to ignition, listen for a clicking sound at the Pilot
ignition solenoid valve to ensure it is opening.
11. Remove and inspect the ignition piece for blockage.
Remove and inspect the Flame Detector for signs of wear or
1.
cracked ceramic. Replace if necessary.
Check gas pressure readings using a gauge or manometer into
2.
and out of the Air/Fuel Valve to ensure that the gas pressure into
and out of the valve is correct.
Check combustion calibration using procedures in Section 4.5 of
3.
the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-
0117 (GF-202).
Remove the burner and inspect for any carbon build-up or debris.
4.
Clean and reinstall.
5.
Remove blockage in condensate drain.
Straighten or replace Main Flame Detector
6.
1.
Press CLEAR button and restart the unit. If the fault persists,
replace Ignition/Stepper (IGST) Board.
Defective relay. Replace IGST Board.
2.
Check combustion calibration using procedures in Section 4.5 of
1.
the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-
0117 (GF-202).
2.
If exhaust temperature is greater than 200
combustion calibration. Calibrate or repair as necessary.
Page 67 of 148
o
o
F (93.3
C), check