Setting The Setpoint; Remote Setpoint Modes - Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 3 – MODES OF OPERATION

3.2.1 Setting the Setpoint

The setpoint temperature of the unit is adjustable from 40°F to 240°F (4.4°C to 115.6°C). To set
the unit for operation in the CONSTANT SETPOINT mode, the following menu settings must be
made in the Configuration menu:
TABLE 3-1: Constant Setpoint Mode Settings
MENU OPTION
SETTING
Boiler Mode
Constant Setpoint
Select desired setpoint using ▲ and ▼ arrow
Internal Setpt
keys (40°F to 240°F,
Refer to Section 2.3, above, for detailed instructions on changing C-More Controller menu
options.

3.3 REMOTE SETPOINT MODES

The unit's setpoint can be remotely controlled by an Energy Management System (EMS) or
Building Automation System (BAS). The Remote Setpoint can be driven by a current or voltage
signal within the following ranges:
4-20 mA/1-5 VDC
0-20 mA/0-5 VDC
The factory default setting for the REMOTE SETPOINT mode is 4 - 20 mA/1 - 5 VDC. With this
setting, a 4 to 20 mA/1 to 5 VDC signal, sent by an EMS or BAS, is used to change the unit's
setpoint. The 4 mA/1V signal is equal to a 40°F (4.4°C) setpoint while a 20 mA /5V signal is
equal to a 240°F (115.6°C) setpoint. When a 0 to 20 mA/0 to 5 VDC signal is used, 0 mA is
equal to a 40°F (4.4°C) setpoint.
In addition to the current and voltage signals described above, the REMOTE SETPOINT mode
can also driven by a RS-485 Modbus Network signal from an EMS or BAS.
The REMOTE SETPOINT modes of operation can be used to drive single as well as multiple
units.
NOTE:
If a voltage, rather than current signal is used to control the remote setpoint, a DIP switch
adjustment must be made on the PMC Board located in the C-More Controller assembly.
Contact your local AERCO representative for details.
In order to enable the REMOTE SETPOINT mode, the following menu setting must be made in
the Configuration menu:
TABLE 3-2: Remote Setpoint Mode Settings
MENU OPTION
SETTING
Boiler Mode
Remote Setpoint
Remote Signal
4-20mA/1-5V, 0-20mA/0-5V, or Network
Refer to Section 2.3 for detailed instructions on changing C-More Controller menu options.
OMM-0118_B • GF-203 • 5/9/2019
4.4°C to 115.6°C)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Page 32 of 148