SECTION 2: OPERATION
TABLE 2-8: Calibration Menu
MENU ITEM DISPLAY
14
Exhst Module Temp
15
Exhst Warn Temp
16
Exhst Tmp VP Adj
17
Exhst Adj Rate
18
VP Change Rate
19
VP Up Rate
20
VP Down Rate
21
Purge Blwr Offst
22
4-20mA Purge Pct
23
PWM In Adj
24
Analog In Adj
25
Flow In Adj
26
Supply Gas Pressure In Adj
27
Gas Plate dp In Adj
28
mA Out Adj
29
A/F Sensitivity
30
Power Reset
31
Water Temp Reset
32
Gas Press Reset
33
Min Off Time
34
Stop Level
35
Start Level
36
Skip Range Cntr
37
Skip Range Span
38
Skip Speed
39
O2 Gain
40
O2 Offset
41
O2 Sensor
42
Cal Temp Sensors
43
FFWD Temp Offset
44
Exhst Tmp Offset
45
Outdr Air Offset
OMM-0118_B • GF-203 • 5/9/2019
AVAILABLE CHOICES OR LIMITS
Minimum
100 °F
100 °F
0
1
5
0.5
0.5
-1.0
60%
-5.0%
-5.0%
-5.0%
-5.0%
-5.0%
-1.0 mA
1%
Automatic or Manual
Automatic or Manual
Automatic or Manual
0 Min
0%
Stop Level
10
0
0.5
0.500
-24.0
Enabled or Disabled
Off or Start
-20
-20
-20
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Maximum
500 °F
500 °F
10
600
600
60.0
Depends on unit type/size
60.0
Depends on unit type/size
8.0
Depends on unit type/size
100%
5.0%
5.0%
5.0%
5.0%
5.0%
1.0 mA
5%
15 Min
Start Level
40%
95
3
2.0
1.500
+2.0
Depends on unit type/size
+20
+20
+20
DEFAULT
190 °F
180 °F
5
30
25
70%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0 mA
2%
Automatic
Automatic
Manual
0 Min
16
20
40
0
0.5
1.024
0
Off
0
0
0