Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
* NOTE:
The 1 BST Units 8 menu item shows the current status for each unit controlled by BST, up
to a maximum of 8 units. The possible characters displayed are:
- = Off Line
* = Not Available (fault, etc.)
0 = Off
1 = On,
A = Lead On
a = Lead Off
B = Lag On
b = Lag Off
S = Setpoint Limit Active
The following example shows the status of 5 units being controlled by BST where:
Unit 1 & 3 are On
Unit 2 is Off
Unit 4 is Not Available
Unit 5 is Lead On
Unit 6 is Lag Off
1 BST Units 8
1
0

2.10 CALIBRATION MENU

The Calibration menu is used by factory trained service personnel to adjust or reset the
parameters listed below.
A full description of each item appears in Table A-6 of Appendix A.
TABLE 2-8: Calibration Menu
MENU ITEM DISPLAY
1
Stepper Fbk
2
Purge Timer
3
Post Purge Timer
4
IGN Position
5
Ign Pos Hold Tmr
6
FFWD Temp Disply
7
Outlet Tmp Dsply
8
Inlet Tmp Dsply
9
Valv Pos Out Dsp
10
Exhaust Tmp Dsp
11
Exhaust Safety
12
Flue Material
13
Exhst Fault Temp
OMM-0118_B • GF-203 • 5/9/2019
1
*
AVAILABLE CHOICES OR LIMITS
Minimum
Cal 0%, Verify 50%, Cal 100%
5 sec.
0 sec.
5%
0 sec.
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
PVC
100 °F
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
A
b
Maximum
60 sec
Depends on unit type/size
60 sec.
60%
Depends on unit type/size
60 sec.
Stainless
500 °F
DEFAULT
Cal 0%
0 sec.
0 sec.
Disabled
Disabled
Disabled
Enabled
Disabled
Enabled
PVC
200 °F