SECTION 2: OPERATION
TABLE 2-7: BST Menu
MENU ITEM DISPLAY
47
BST Setpt HI Limit
48
BST Prop Band
49
BST Intgral Gain
50
BST Deriv Time
51
BST Deadband Hi
52
BST Deadband Lo
53
Deadband En Time
54
BST FR Up Rate
55
BST Bldg Ref Tmp
56
BST Reset Ratio
57
System Start Tmp
58
*BST COMM MENU*
59
Comm Address
60
BST Min Addr
61
BST Max Addr
62
SSD Address
63
SSD Poll Control
64
Err Threshold
65
SSD Temp Format
66
BST Upld Timer
OMM-0118_B • GF-203 • 5/9/2019
AVAILABLE CHOICES OR LIMITS
Minimum
BST Setpt Lo Limit
1°F (-17.2°C)
0.00
0.00 Min
0
0
0
1
40°F (4.4°C)
0.1
30°F (-1.1°C)
Disabled
0
1
1
0
0
1
Degrees
0
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Maximum
220°F (104.4°C)
120°F (48.9°C)
2.00
2.00 Min
25
25
120 Sec
120
230°F (110°C)
9.9
120°F (48.9°C)
Enabled
127
128
128
250
1000
9
Points
9999 sec
DEFAULT
195°F (90.6°C)
100°F (37.8°C)
0.50
0.10 Min
1
1
30 Sec
20
70°F (21.1°C)
1.2
60°F (15.6°C)
Disabled
0
1
8
247
0
5
Degrees
0