Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual page 96

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
TABLE A-3: CONFIGURATION Menu Item Descriptions
MENU OPTIONS
25
Deadband High
26
Deadband Low
27
IGST Version
28
IGN Time Setting
29
Slow Shutdown
30
Slow Sht Duration
31
Slow Sht Threshold
32
O2 Warnings
33
O2 Trim ID
34
Fixed ID
35
O2 Trim Key
36
O2 Trim Menu
37
BST Menu
OMM-0118_B • GF-203 • 5/9/2019
Deadband High and Deadband Low settings create an "Outlet
Temperature" Zone in which no Valve Position corrections will
be attempted.
The Deadband ZONE is defined as operating with an Outlet
Temperature between Active Setpoint + Deadband High and
Active Setpoint – Deadband Low.
When the Outlet Temperature reaches Active Setpoint and
remains there for a period of 15 seconds, the unit will go into a
DEADBAND MODE at which point no Valve Position
corrections will be attempted while the Outlet Temperature
remains anywhere within the Deadband ZONE. When the unit
is in the DEADBAND MODE, the °F or °C LED will flash on and
off. When the Outlet Temperature drifts out of the Deadband
ZONE, the DEADBAND MODE will be terminated and the PID
LOOP will again attempt Valve Position corrections.
Setting range is 0°F (0°C) to 25°F (13.75°C). Default is 5°F
(2.75°C) for both Deadband High and Deadband Low).
Displays the version of the IGST Board installed.
Displays the MAX Ignition time of 4 Seconds or 7 Seconds as
set in the Safety String Harness.
Set the Slow Shutdown feature to Enabled or Disabled.
If Slow Shutdown = Enabled, sets the time a boiler will
continue to run at the Stop Level after running above the Slow
Sht Threshold level, up to 9,999 seconds.
Sets the Fire Rate above which a boiler will trigger the Slow
Shutdown feature.
Enables or disables AERtrim warning messages.
Displays 4 digit AERtrim ID number. Pre-populated on some
units. Changes each time the unit is powered up.
Displays the unit's fixed 4 digit ID number. Pre-populated on
some units. Does not change.
Displays the value of the AERtrim 4 digit license key. Pre-
populated on some+ units.
When set to Enabled, the AERtrim menu options appears.
When set to Enabled, the BST menu options appears.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DESCRIPTION
Page 96 of 148