Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual page 93

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
TABLE A-2: SETUP MENU ITEM DESCRIPTIONS
See Section 2-5 for a range of choices and the default values.
TABLE A-2: SETUP Menu Item Descriptions
MENU OPTIONS
1
Password
2
Language
3
Time
4
Date
5
Unit of Temp
6
Comm Address
7
Baud Rate
8
onAER Mode
9
Min Upload Timer
10
Unit Alpha
11
Unit Year
12
Unit Serial #
13
Software Version
OMM-0118_B • GF-203 • 5/9/2019
Allows Level 1 or Level 2 password to be entered.
Entering the Level 1 Password (159) allows options in the Setup,
Configuration and Tuning menus to be modified.
Entering the Level 2 Password (6817) allows options in the
Calibration and Diagnostics Menus to be changed or activated, in
addition to all Level 1 Menu options.
Permits selection of the language of displayed messages. English is
the only option at this time.
Displays time from 12:00 am to 11:59 pm.
Displays dates from 01/01/00 to 12/31/99
Permits selection of temperature displays in degrees Fahrenheit (°F)
or degrees Celsius (°C).
For RS-485 communications. RS232 should have its own
(programmable) password.
Allows communications Baud Rate to be set (2400 to 19.2K).
Default is 9600.
Allows selection of either Ethernet or SD Card.
Mandatory for AERCO onAER Remote Data Collection (ORDC).
This parameter enables ORDC and defines the minimum amount of
time between heartbeat data uploads in seconds. The COMM LED
will light during the upload.
Mandatory for AERCO onAER Remote Data Collection. This value
must match the first alpha digit on the Code Plate, e.g.,
Mandatory for AERCO onAER Remote Data Collection. This value
must match the 2-digit year on the Code Plate, e.g., G-
Mandatory for AERCO onAER. Remote Data Collection. This value
must match the 4-digit serial # on the Code Plate, e.g., G-12-
Identifies the current software version of the C-More Controller.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DESCRIPTION
G
-12-1234.
12
-1234.
1234
.
Page 93 of 148