Watts Aerco Benchmark OMM-0117 Operation And Maintenance Manual page 94

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
TABLE A-3: CONFIGURATION MENU ITEM DESCRIPTIONS
See Section 2-6 for a range of choices and the default values.
The Configuration menu settings are Factory-Set in accordance with the requirements specified
with each individual order. No changes will be required under normal operating conditions.
TABLE A-3: CONFIGURATION Menu Item Descriptions
MENU OPTIONS
1
Internal Setpoint
2
Unit Type
3
Unit Size
4
Fuel Type
5
Boiler Mode
6
Remote Signal
7
Outdoor Sensor
8
Bldg Ref Temp
9
Reset Ratio
10
System Start Tmp
11
Setpt Lo Limit
12
Setpt Hi Limit
13
Temp Hi Limit
14
Max Valve Position
15
Pump Delay Timer
OMM-0118_B • GF-203 • 5/9/2019
Allows internal setpoint to be set from Lo Temp Limit of 40°F to
Hi Temp Limit of 240°F (4.4°C to 115.6°C).
Can be one of the following: BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual.
Sets unit size, depending on the Unit Type:
Benchmark 5000 – 5000 MBH (1465 kW)
Benchmark 6000 – 6000 MBH (1758 kW)
Allows selection of Natural Gas or Propane.
Only available if Unit Type = Boiler. Allows selection of:
Constant Setpoint, Remote Setpoint, Direct Drive,
Combination, or Outdoor Reset Mode.
Only available if Mode = Remote Setpoint, Direct Drive or
Combination. Used to set the type of external signal which will
be used when operating in the Remote Setpoint, Direct Drive
or Combination Mode.
Allows outdoor sensor function to be set to Enabled or
Disabled.
Only available if Boiler Mode = Outdoor Reset. Allows the
building reference temperature to be set when operating a
boiler in the Outdoor Reset Mode.
Only available if Boiler Mode = Outdoor Reset. Permits setting
of Reset Ratio when operating boiler in the Outdoor Reset
Mode.
Only if Outdoor Sensor = Enabled. This menu item allows the
system start temperature to be set.
Used to set the minimum allowable setpoint, from 40°F (4.4
up to the Setpt Hi Limit.
Used to set the maximum allowable setpoint, from the Setpt Lo
Limit up to 210°F (98.9
This is the maximum allowable outlet temperature, up to 210°F
(98.9
. Any temperature above this setting will turn off the
°C)
unit. The temperature must then drop 5°F (2.75
setting to allow the unit to run.
Sets the maximum allowable valve position for the unit.
Specifies the amount of time, up to 30 minutes, to keep the
pump running after the unit turns off.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DESCRIPTION
.
°C)
°C)
below this
°C)
Page 94 of 148

Advertisement

Table of Contents
loading

Table of Contents