APPENDIX A: BOILER MENU DESCRIPTIONS
TABLE A-1: OPERATING Menu Item Descriptions
MENU OPTIONS
16
Air Pump Voltage
17
Run Cycles
18
Run Hours
19
Fault Log
20
Manual Valve Pos
OMM-0118_B • GF-203 • 5/9/2019
A voltage signal proportional to the current drawn by the Air
Eductor's Air Pump. This pump draws a sample of gas across the
O
sensor anytime the boiler has proven flame operation.
2
If Air Pump voltage is less than 0.20V or greater than 1.20V for
more than 10 seconds, a AIR PUMP FAILED / O2 TRIM
DISABLED message is generated. It can only be cleared by
pressing the CLEAR button on C-More Controller.
Displays the total number of run cycles.
Displays total run time of unit in hours.
Displays information on the last 20 faults.
Selects valve position. Available in Manual mode only!
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
DESCRIPTION
Page 92 of 148