Electrical Installation
Terminal
Parameter
68 (+)
Parameter
group 8-3* FC
Port Settings
69 (-)
Parameter
group 8-3* FC
Port Settings
Table 5.1 Serial Communication Terminal Descriptions
Digital input/output terminals
Terminal
Parameter
12, 13
+24 V DC
18
Parameter 5-10
[8] Start
Terminal 18
Digital Input
19
Parameter 5-11
Terminal 19
Reversing
Digital Input
32
Parameter 5-14
Terminal 32
operation
Digital Input
33
Parameter 5-15
Terminal 33
operation
Digital Input
27
Parameter 5-12
[2] Coast
Terminal 27
Digital Input
29
Parameter 5-13
[14] JOG
Terminal 29
Digital Input
20
37
Table 5.2 Digital Input/Output Terminal Descriptions
MG38A202
Operating Guide
Default
Description
setting
RS485 interface. A
switch (BUS TER.) is
provided on the
control card for bus
termination
resistance. See
Illustration 5.23.
Default
Description
setting
24 V DC supply
voltage for digital
inputs and external
transducers.
Maximum output
current 200 mA for all
24 V loads.
Digital inputs.
[10]
[0] No
[0] No
For digital input or
inverse
output. Default
setting is input.
Common for digital
inputs and 0 V
potential for 24 V
supply.
STO
When not using the
optional STO feature,
a jumper wire is
required between
terminal 12 (or 13)
and terminal 37. This
set-up allows the
drive to operate with
factory default
programming values.
Danfoss A/S © 04/2018 All rights reserved.
Analog input/output terminals
Terminal
Parameter
Default
39
42
Parameter 6-50
Terminal 42
operation
Output
50
+10 V DC
53
Parameter
Reference
group 6-1*
Analog Input 1
54
Parameter
Feedback
group 6-2*
Analog Input 2
55
Table 5.3 Analog Input/Output Terminal Descriptions
5.8.3 Relay Terminals
RELAY 1
RELAY 2
01
02 03
04
05 06
Illustration 5.19 Relay 1 and Relay 2 Terminals
Relay 1 and relay 2. The location of the outputs
depends on the drive configuration. See
chapter 3.5 Control Shelf.
Terminals on built-in optional equipment. See the
manual provided with the equipment option.
Terminal
Parameter
Default
01, 02, 03
Parameter 5-40
Function Relay
operation
[0]
04, 05, 06
Parameter 5-40
Function Relay
operation
[1]
Table 5.4 Relay Terminal Descriptions
Description
setting
Common for analog
output.
[0] No
Programmable analog
output. 0–20 mA or
4–20 mA at a
maximum of 500 Ω.
10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum.
Analog input. For
voltage or current.
Switches A53 and
A54 select mA or V.
Common for analog
input.
Description
setting
[0] No
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
[0] No
41
5
5