Mechanical Installation
4.8.3 Installing Load share/Regeneration Terminals
The load share/regeneration terminals, located on the top
of the drive, are not installed from the factory to prevent
damage during shipping. Refer to Illustration 4.9 for the
following steps.
1
2
3
4
5
1 Label fastener, M4
2 Label
3 Load share/regeneration terminal
4 Terminal fastener, M10
5 Terminal plate with 2 openings
Illustration 4.9 Load share/Regeneration Terminals
MG38A202
Operating Guide
1.
2.
3.
4.
5.
Danfoss A/S © 04/2018 All rights reserved.
Remove the terminal plate, 2 terminals, label, and
fasteners from the accessory bag included with
the drive.
Remove the cover from the load share/
regeneration opening on the top of the drive. Put
aside the 2 M5 fasteners for reuse later.
Remove the plastic backing and install the
terminal plate over the load share/regeneration
opening. Secure with the 2 M5 fasteners and
torque to 2.3 Nm (20 in-lb).
Install both terminals to the terminal plate using
1 M10 fastener per terminal. Torque to 19 Nm
(169 in-lb).
Install the label on the front of the terminals as
shown in Illustration 4.9. Secure with 2 M4 screws
and torque to 1.2 Nm (10 in-lb).