Siemens airanger DPL PLUS Instruction Manual page 52

Table of Contents

Advertisement

Setpoints
ON OFF Status Alarm
Level H or HH
85%
Level L or LL
15%
L
80%
In bounds
Out of bounds
80%
L
Rate of change +10% +5%
-10% -5%
Temperature
-30
Pump
80%
20%
* Values shown are for illustration purposes only. Enter values which apply to your
particular installation.
L 2% factory set deadband, adjustable via P116
Page 46
70%
On
Off
30%
On
Off
50%
On
Off
On
Off
50%
Off
On
Off
On
Off
On
Off
On
60
55
On
Off
-25
On
Off
20%
On
Off
80%
On
Off
AiRanger DPL Plus – INSTRUCTION MANUAL
Action
Relay
On
de-energizes
Off
energizes
On
de-energizes
Off
energizes
On
de-energizes
Off
energizes
On
de-energizes
Off
energizes
Off
energizes
On
de-energizes
Off
energizes
On
de-energizes
Off
de-energizes
Fill rate increases to 10%/min
On
energizes
Off
de-energizes Empty rate increases to 10%/min
On
energizes
Empty rate decreases to 5%/min
On
de-energizes
Off
energizes
On
de-energizes
Off
energizes
On
energizes
Start pump down on level at 80%
Off
de-energizes Stop pump down on level at 20%
On
energizes
Start pump up on level at 20%
Off
de-energizes
Stop pump up on level at 80%
When
Level rises to 85%
Level falls to 70%
Level falls to 15%
Level rises to 30%
Level falls to 78%
Level rises to 82%
Level rises to 52%
Level falls to 48%
Level falls to 78%
Level rises to 82%
Level rises to 52%
Level falls to 48%
Fill rate decreases to 5%/min
Temperature rises to 60°C
Temperature falls to 55°C
Temperature falls to -30°C
Temperature rises to -25°C
7ML19981BD02