P334 Auto Record ON Setpoint
Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Primary Index
Values
Related
P335 Auto Record OFF Setpoint
Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
Primary Index
Values
Related
P336 Auto Record Filling / Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
Primary Index
Values
Related
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
Page 56
Global
Range: -999 to 9999
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Global
Range: -999 to 9999
P334 Auto Record ON Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Global
0
*
Auto Profile Record on filling or emptying
1
Auto Profile Record on filling only
2
Auto Profile Record on emptying only
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P337 Auto Record LOE Time
P702 Filling Indicator
P703 Emptying Indicator