YASKAWA FP605 Installation & Primary Operation page 82

Ac drive for industrial fan and pump applications
Hide thumbs Also See for FP605:
Table of Contents

Advertisement

12 UL Standards
Table 12.3 Required Short Circuit Protection for FP605 AC Drives (480 V Class)
Drive Mounted without
Supplemental Enclosure
(Using Type 1 Kit)
Drive
Semiconductor
Catalog
*1
Code
Fuse
Part Number
Class CC, J, or T
FP65U
(Permitted Only
in Type 1 Kit)
Maximum Amps
Manufacturer:
Eaton/Bussmann
4005
4006
4008
4011
4014
4021
4027
4034
4040
Not allowed.
4052
Does not support
4065
internal fuses for
these drive models.
4077
4096
4124
4156
4180
4240
4302
4361
FWH‐800A
FWH-1000A
4414
or
FWH-1000B
FWH-1200A
Not allowed.
4477
or
Must use
FWH-1200B
semiconductor
fuses.
FWH-1200A
4515
or
FWH-1200B
4590
FWH-1400A
4720
FWH-1400A
*1
Protection device must be in same enclosure with drive.
*2
Class T fuses are fast-acting (non‐time-delay) only. Class CC and J can be either time-delay or non-time-delay.
*3
Protection device and drive permitted in same or separate enclosure.
*4
External heatsink installation on these models requires a heatsink shroud and filter.
82
Any Size Protected Enclosure
(Ventilated or Non-Ventilated)
Semiconductor
*1
Fuse
*2
Fuse
Part Number
Manufacturer:
Eaton/Bussmann
8
FWH‐25A14F
9
FWH‐30A14F
12
FWH‐30A14F
17.5
FWH‐40B
20
FWH‐45B
35
FWH‐60B
45
FWH‐80B
60
FWH‐100B
70
FWH‐125B
90
FWH‐150B
110
FWH‐200B
125
FWH‐225A
150
FWH‐225A
200
FWH‐225A
250
FWH‐325A
300
FWH‐500A
400
FWH‐600A
500
FWH‐700A
FWH‐800A
FWH-1000A
or
FWH-1000B
FWH-1200A
Not allowed.
or
Must use minimum
FWH-1200B
enclosure volume
requirements.
FWH-1200A
or
FWH-1200B
FWH-1400A
FWH-1400A
Drive Mounted in Supplemental Enclosure
Class CC, J, or T
Class CC, J, or T
*2 *3
*2 *3
Fuse
Fuse
Maximum Amps
Maximum Amps
8
9
12
17.5
20
35
45
60
70
Enclosure volume
90
not restricted.
Refer to the values
110
in the column to the
left for fuses.
125
150
200
250
300
400
500
600
700
800
900
1000
1200
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Restricted Size Protected Enclosure
(Ventilated Only)
*1
MCP
*3
MCCB
Part Number
Maximum
Manufacturer:
Amps
External
Schneider
Heatsink
15
HLL36030M71
15
HLL36030M71
15
HLL36030M71
25
HLL36030M71
35
HLL36030M71
50
HLL36030M71
60
HLL36050M72
80
HLL36050M72
100
HLL36100M73
125
HLL36100M73
150
HLL36100M73
175
HLL36100M73
225
HLL36150M74
300
JLL36250M75
350
JLL36250M75
450
JLL36250M75
52800
LAL3640036M
600
or
52800
LLL36400M37X
LAL3640036M
700
or
52800
LLL36400M37X
700
PLL34060M68
52800
800
PLL34060M68
52800
900
PLL34080M68
52800
1000
PLL34080M68
52800
1200
PLL34080M68
52800
1400
PLL34100M69
52800
Enclosure Volume
3
Minimum (in
)
Internal
Heatsink
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
3056
5520
5520
5520
5520
5520
5520
5520
5520
5520
5520
5520
5520
21582
14657
*4
14657
*4
14657
*4
14657
*4
52800
*4
52800
*4
52800
*4
52800
*4
52800
*4
52800

Advertisement