Model
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2031
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2046
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2059
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2075
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2088
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2114
-, +1
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Applicable Gauge
Recommended
Gauge
AWG, kcmil
AWG, kcmil
(mm
2
)
*1
14 - 8
8
(2.5 - 10)
14 - 8
8
(2.5 - 10)
14 - 8
8
(2.5 - 10)
14 - 8
10
(2.5 - 10)
14 - 4
8
(2.5 - 25)
14 - 4
6
(2.5 - 25)
14 - 4
6
(2.5 - 25)
14 - 4
8
(2.5 - 25)
14 - 4
4
(2.5 - 25)
14 - 4
4
(2.5 - 25)
14 - 4
4
(2.5 - 25)
14 - 4
6
(2.5 - 25)
8 - 2/0
4
(10 - 70)
8 - 2/0
3 or 2
(10 - 70)
8 - 2/0
2
(10 - 70)
8 - 2/0
6
(10 - 70)
8 - 2/0
3 or 2
(10 - 70)
8 - 2/0
2
(10 - 70)
8 - 2/0
1
(10 - 70)
8 - 2/0
6
(10 - 70)
8 - 2/0
1/0
(10 - 70)
8 - 2/0
1/0
(10 - 70)
8 - 2/0
2/0
(10 - 70)
8 - 2/0
6
(10 - 70)
*2
IP20 Applicable Gauge
Wire Stripping
AWG, kcmil
Length
*1
(mm
2
)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7 Electrical Installation
Terminal Screw
Tightening Torque
*3
Size and Shape
N∙m (lbf∙in)
mm
10
M4
10
M4
10
M4
-
M5
(17.7 - 22.1)
18
M5
18
M5
18
M5
-
M6
(35.4 - 44.3)
18
M5
18
M5
18
M5
-
M6
(35.4 - 44.3)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(79.7 - 97.4)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(79.7 - 97.4)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(47.8 - 53.1)
-
M8
(79.7 - 97.4)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
2.0 - 2.5
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
4.0 - 5.0
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
4.0 - 5.0
5.4 - 6.0
5.4 - 6.0
5.4 - 6.0
9.0 - 11
5.4 - 6.0
5.4 - 6.0
5.4 - 6.0
9.0 - 11
5.4 - 6.0
5.4 - 6.0
5.4 - 6.0
9.0 - 11