Advertisement

Item
Select from 15 pre-defined V/f patterns, or a user-set V/f pattern.
V/f Characteristics
Restart After Momentary Power Loss, Speed Search, Overtorque/Undertorque Detection, Torque Limit, 17 Step Speed (max.), Accel/Decel Switch, S-curve
Acceleration/Deceleration, 3-wire Sequence, Auto-Tuning (Rotational and Stationary), Dwell Function, Cooling Fan ON/OFF Switch, Slip Compensation,
Main Control
Torque Compensation, Jump Frequency, Upper/Lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, Overexcitation Braking, High
Functions
Slip Braking, PID Control (with Sleep Function), Energy Saving Control, MEMOBUS/Modbus Communication (RS-485 max. 115.2 kbps), Auto Restart,
Application Presets, KEB, Overexcitation Deceleration, Overvoltage Suppression
Item
Electronic thermal overload protection
Motor Protection
Momentary
Drive stops when the output current is more than 175% of the drive rated output current.
Overcurrent
Protection
Drive stops when the output current is more than these overload tolerances:
• 110% of the rated output current for 60 seconds
• 140% of the rated output current for 2.5 seconds when the drive output frequency is 3 Hz
Overload Protection
The permitted frequency of overload is one time each 10 minutes.
Note:
If output frequency < 6 Hz, the drive can trigger the overload protection function when the output current is in the overload tolerance range.
Overvoltage
208 V class: Stops when the DC bus voltage is more than approximately 410 V
Protection
480 V class: Stops when the DC bus voltage is more than approximately 820 V
208 V class: Stops when the DC bus voltage decreases to less than approximately 190 V
480 V class:
Undervoltage
• Stops when the DC bus voltage decreases to less than approximately 350 V when you use an input voltage less than 400 V
Protection
• Stops when the DC bus voltage decreases to less than approximately 380 V when you use an input voltage less than 460 V
• Stops when the DC bus voltage decreases to less than approximately 440 V when you use an input voltage of 460 V or more
Immediately stops when power loss is 15 ms or longer.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Momentary Power
Loss Ride-thru
Note:
Stop time may be shortened depending on the load and motor speed.
Heatsink Overheat
The drive stops when the thermistor detects an IGBT temperature more than approximately 100 °C (212 °F). The trip temperature level is different for different
Protection
drive models.
Stall prevention is available during acceleration, deceleration, and during run.
Stall Prevention
Electronic circuit protection
Note:
Ground Fault
This protection detects ground faults during run. The drive will not provide protection when:
Protection
• There is a low-resistance ground fault for the motor cable or terminal block
• Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Item
Indoors
Area of Use
Overvoltage Category III
Power Supply
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
Ambient Temperature
Setting
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
• You can use IP20/UL Open Type and IP20/UL Type 1 drives at a maximum of 60 °C (140 °F) when you derate the output current.
• You can use IP55/UL Type 12 drives at a maximum of 50 °C (122 °F) when you derate the output current.
95% RH or less
Humidity
Do not let condensation form on the drive.
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Storage Temperature
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Specification
Table 5.2 Protection Functions
Specification
Table 5.3 Environment
Specification
5 Common Drive Specifications
13