A - UL Recognized heat-shrinkable tube
Comply with local standards for correct wire gauges in the region where the drive is used.
Refer to
Table 12.1
to select ferrules and crimp terminals as specified by drive model and wire gauge.
Note:
To comply with UL standards, use UL Listed vinylcoated insulated copper wires for operation with a continuous maximum permitted
temperature of 75 °C at 600 V.
Model
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2011
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2017
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2024
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2031
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2046
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2059
-, +1
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Table 12.1 Ferrules and Closed-Loop Crimp Terminals
Recommended
Gauge
Ferrule
AWG, kcmil
14
F80-10
14
F80-10
14
F80-10
12
12
F81-10
10
F82-10
10
F82-10
10
10
F82-10
8
F83-12
8
F83-12
10
8
F83-12
8
F83-12
8
F83-12
10
8
F83-18
6
F84-18
6
F84-18
8
4
F85-18
4
F85-18
4
F85-18
6
Crimp Terminal Part Number
Manufacturer: PANDUIT Corp.
*1
Type LCA
N/A
N/A
N/A
N/A
LCA10-14-L
N/A
N/A
N/A
N/A
LCA10-14-L
N/A
N/A
N/A
N/A
LCA10-14-L
N/A
N/A
N/A
N/A
LCA10-14-L
N/A
N/A
N/A
N/A
LCA8-14-L
N/A
N/A
N/A
N/A
LCA6-14-L
12 UL Standards
Type P
Type S
N/A
N/A
N/A
N/A
N/A
N/A
P10-14R-L
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P10-14R-L
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P10-14R-L
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P10-14R-L
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P8-14R-Q
S8-14R-Q
N/A
N/A
N/A
N/A
N/A
N/A
P6-14R-E
S6-14R-E
75