Required Short Circuit Protection
Table 12.2 Required Short Circuit Protection for FP605 AC Drives (240 V Class)
Drive Mounted without
Supplemental Enclosure
(Using Type 1 Kit)
Drive
Semiconductor
Catalog
Fuse
*1
Code
Part Number
Class CC, J, or T
FP65U
(Permitted Only
in Type 1 Kit)
Maximum Amps
Manufacturer:
Eaton/Bussmann
2011
2017
2024
2031
2046
2059
2075
2088
2114
Not allowed.
2143
Does not support
internal fuses for
2169
these drive models.
2211
2273
2343
2396
*1
Protection device must be in same enclosure with drive.
*2
Class T fuses are fast-acting (non‐time-delay) only. Class CC and J can be either time-delay or non-time-delay.
*3
Protection device and drive permitted in same or separate enclosure.
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Any Size Protected Enclosure
(Ventilated or Non-Ventilated)
Semiconductor
Fuse
*1
Fuse
*2
Part Number
Manufacturer:
Eaton/Bussmann
17.5
FWH‐40B
25
FWH‐45B
40
FWH‐80B
50
FWH‐125B
80
FWH‐125B
100
FWH‐175B
125
FWH‐200B
150
FWH‐225A
200
FWH‐225A
250
FWH‐250A
250
FWH‐275A
350
FWH‐600A
450
FWH‐800A
FWH-1000A
600
or
FWH-1000B
FWH-1000A
700
or
FWH-1000B
Drive Mounted in Supplemental Enclosure
Class CC, J, or T
Class CC, J, or T
Fuse
*2 *3
Fuse
*2 *3
Maximum Amps
Maximum Amps
17.5
25
40
50
80
100
125
150
200
Enclosure volume
not restricted.
250
Refer to the values
250
in the column to the
left for fuses.
350
450
600
700
12 UL Standards
Restricted Size Protected Enclosure
(Ventilated Only)
*1
MCP
*3
MCCB
Part Number
Maximum
Manufacturer:
Amps
External
Schneider
Heatsink
25
HLL36030M71
40
HLL36030M71
60
HLL36050M72
75
HLL36050M72
110
HLL36100M73
125
HLL36100M73
175
HLL36150M74
200
HLL36150M74
250
HLL36150M74
350
JLL36250M75
400
JLL36250M75
LAL3640036M
500
or
LLL36400M37X
LAL3640036M
600
or
LLL36400M37X
700
PLL34060M68
800
PLL34060M68
Enclosure Volume
Minimum (in
3
)
Internal
Heatsink
3056
3056
3056
3056
3056
3056
3056
3056
5520
5520
5520
5520
5520
5520
5520
5520
5520
5520
21582
14657
21582
14657
52800
14657
52800
14657
52800
52800
52800
52800
81