YASKAWA FP605 Installation & Primary Operation page 34

Ac drive for industrial fan and pump applications
Hide thumbs Also See for FP605:
Table of Contents

Advertisement

7 Electrical Installation
Model
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2143
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2169
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2211
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2273
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2343
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2396
-, +1
*1
The metric wire gauge values are provided as reference information from equivalent AWG sizes and not exactly the same sizes as the
AWG/kcmil values. Obey local safety regulations for wire sizes and make sure that the ferrule or crimp terminals are correct for your size.
*2
For IP20 protection, use wires that are in the range of applicable gauges.
*3
Remove insulation from the ends of wires to expose the length of wire shown.
34
Applicable Gauge
Recommended
Gauge
AWG, kcmil
AWG, kcmil
(mm
2
)
*1
6 - 4/0
2/0
(16 - 95)
6 - 4/0
3/0
(16 - 95)
6 - 4/0
3/0
(16 - 95)
6 - 4/0
4
(16 - 95)
6 - 4/0
3/0
(16 - 95)
6 - 4/0
4/0
(16 - 95)
6 - 4/0
1/0 × 2
(16 - 95)
6 - 4/0
4
(16 - 95)
3 - 4/0 × 2P
1/0 × 2
(25 - 95 × 2P)
3 - 4/0 × 2P
1/0 × 2
(25 - 95 × 2P)
2 - 250 × 2P
2/0 × 2
(35 - 120 × 2P)
4 - 350
3 or 2
(25 - 185)
3 - 4/0 × 2P
2/0 × 2
(25 - 95 × 2P)
3 - 4/0 × 2P
2/0 × 2
(25 - 95 × 2P)
2 - 250 × 2P
4/0 × 2
(35 - 120 × 2P)
4 - 350
2
(25 - 185)
2/0 - 300 × 2P
4/0 × 2
(70 - 150 × 2P)
2/0 - 300 × 2P
4/0 × 2
(70 - 150 × 2P)
4/0 - 400 × 2P
250 × 2
(95 - 185 × 2P)
1 - 350
1/0
(50 - 185)
2/0 - 300 × 2P
250 × 2
(70 - 150 × 2P)
2/0 - 300 × 2P
250 × 2
(70 - 150 × 2P)
4/0 - 400 × 2P
350 × 2
(95 - 185 × 2P)
1 - 350
1/0
(50 - 185)
*2
IP20 Applicable Gauge
AWG, kcmil
*1
(mm
2
)
-
-
-
-
-
-
-
-
2/0 - 4/0 × 2P
(70 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
4/0 - 250 × 2P
(95 - 120 × 2P)
-
2/0 - 4/0 × 2P
(70 - 95 × 2P)
2/0 - 4/0 × 2P
(70 - 95 × 2P)
4/0 - 250 × 2P
(95 - 120 × 2P)
-
250 - 300 × 2P
(120 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
250 - 300 × 2P
(120 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Wire Stripping
Terminal Screw
Length
*3
Size and Shape
mm
-
M8
-
M8
-
M8
-
M8
-
M8
-
M8
-
M8
-
M8
-
M10
-
M10
-
M10
-
M10
-
M10
-
M10
-
M10
-
M10
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
-
M12
Tightening Torque
N∙m (lbf∙in)
13.5 - 15
(119.5 - 132.8)
13.5 - 15
(119.5 - 132.8)
13.5 - 15
(119.5 - 132.8)
9.0 - 11
(79.7 - 97.4)
13.5 - 15
(119.5 - 132.8)
13.5 - 15
(119.5 - 132.8)
13.5 - 15
(119.5 - 132.8)
9.0 - 11
(79.7 - 97.4)
18 - 20
(159.3 - 177)
18 - 20
(159.3 - 177)
18 - 20
(159.3 - 177)
18 - 23
(159 - 204)
18 - 20
(159.3 - 177)
18 - 20
(159.3 - 177)
18 - 20
(159.3 - 177)
18 - 23
(159 - 204)
31.5 - 35
(279 - 310)
31.5 - 35
(279 - 310)
31.5 - 35
(279 - 310)
32 - 40
(283 - 354)
31.5 - 35
(279 - 310)
31.5 - 35
(279 - 310)
31.5 - 35
(279 - 310)
32 - 40
(283 - 354)

Advertisement

Table of Contents
loading

Table of Contents