EBS CPX200N Installation And Programming Manual page 60

Alarm control unit
Table of Contents

Advertisement

8.3.1.3. Interlocking
The option allows interlocking any input line, which means that any changes of state
at this input are ignored and not reported to monitoring station.
You can set the set permanently blocking input ("Permanent"), or turn on the
blocking after a given number of input violations.
If you select "After time for exit", the input line will be blocked if the line was violated
when arming. In this case, an event about blocked line will be generated, which
allows to inform the monitoring station about the problem with the line. This lock will
last until disarming. If the input is selected as the "Alarm after time for exit", then
"Interlocking after time for exit" has priority - the zone will be blocked and will not
generate an alarm.
If the line is set to "After time for exit" and is violated or sabotaged after the time for
exit, then is automatically bloked (bypass is activated). User can unlock the input by
use the function 50 # (block inputs).
8.3.1.4. Sensitivity
That parameter defines a minimum time the change must maintain at the particular
zone, to be detected by a transmitter. Default factory setting of the parameter is 400
ms.
8.3.1.5. Delay
The parameter is active for delayed type zones only. It defines a time from the zone
disruption was detected after which an alarm is generated.
8.3.1.6. Alarm after time for exit
Enabling this option causes the panel immediately generates an alarm when the zone
was violated when the system is armed.
8.3.1.7. Ignore during arming
Zone can be violated during partition arming (e.g. delay circuits shall be set to that
option).
CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL
60 / 106

Advertisement

Table of Contents
loading

Table of Contents