PSU%_FAN_Speed (% = PSU number)
Sensor Type:
Fan
Event Severity:
Critical
Description:
Upper Non-Recoverable - Going High - Asserted
Message:
PSU FAN speed is too high
Actions:
1. Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to
this error.
2. Check if the fan in the power supply unit is functioning. If not, replace the power supply unit.
3. If the error recurs, contact Lenovo service representative for technical support.
• Diagnostic Code:
0B010BAA
Full Sensor Name (Sensor Name In SDR):
FAN_BP_Power
Sensor Type:
Other Units-based sensor
Event Severity:
Critical
Description:
Upper Non-Recoverable - Going High - Asserted
Message:
FAN backplane power consumption is too high
Actions:
1. Check Lenovo Data Center Support site for an applicable retain tip or firmware update that applies to
this error.
2. reseat all the fans, and make sure they are properly installed.
3. Power cycles the chassis.
4. If the error recurs, contact Lenovo service representative for execution of fan backplane replacement.
• Diagnostic Code:
0B010BAB
Full Sensor Name (Sensor Name In SDR):
HDD_BP_Power
Sensor Type:
Other Units-based sensor
Event Severity:
Critical
Description:
Appendix A. TMM error messages