CHAPTER 4: Installation Instructions
4.15

DETERMINATION OF PRIMARY BOILER PUMP OR BOILER SYSTEM PUMP

The following table gives an indication of the pump's flow rate in function of the
primary circuit if the installation has a mixing header.
The size of the pumps must be determined by installers or technical engineers according to
boiler data and system design.
TABLE 4-2: MODULEX EXT Minimum/Maximum Flow Rates
BOILER MODEL
Min. flow rate demanded in gal/min ∆T 27°F (15°C)
Min. flow rate demanded in gal/min ∆T 36°F (20°C)
Max flow rate demanded in gal/min ∆T 27°F (15°C)
Max flow rate demanded in gal/min ∆T 36°F (20°C)
The water side resistance curve of the boiler is shown in the diagram in Figure 4-19.
The pump is not an integral part of the boiler. It is recommended to choose a pump with the rate
and delivery head at about 2/3 of its characteristic heating curve.
Figure 4-19: MODULEX EXT Water Side Pressure Losses
NOTE:
The use of a mixing header fitted between the boiler circuit and the system circuit is always
advisable. It becomes INDISPENSABLE if the system requires flow rates superior to the
maximum permitted boiler flow rates, which is to say lower than 27° F (15 K).
OMM-0087_J • GF-143 • 11/17/2020
EXT 481/450
EXT 321
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
481/450
641/600
321
6.5
9.7
12.9
4.9
7.3
9.7
22.6
33.8
45.1
16.9
25.4
33.9
EXT
EXT
641
802
800
600
∆t
of the
802/800
1123/1100
962
16.2
19.4
22.7
12.1
14.6
17.0
56.4
67.7
79.0
42.3
50.8
59.3
EXT
1123
EXT
1100
1912