Benchmark 6000 Air/Fuel Valve Position And Energy Input - Watts Aerco Benchmark OMM-0124 Installation And Start-Up Manual

Natural gas, propane gas and dual fuel fired modulating & condensing boilers
Table of Contents

Advertisement

Benchmark 5000-6000 Boiler Installation & Startup Manual
SECTION 3: START SEQUENCE

3.4.2 Benchmark 6000 Air/Fuel Valve Position and Energy Input

BMK 6000 Air/Fuel Valve Position and Energy Input
Air Fuel Valve
Position
(% Full Open)
0%
10%
18% (Stop Level)
20%
30%
40%
50%
60%
70%
80%
90%
BMK 6000 Gas Pressure De-Rating Chart
Gas Pressure @ SSOV
in inches W.C. (kPa)
Inlet
56"
(13.9 kPa)
14"
(3.49 kPa)
13"
(3.23 kPa)
OMM-0123_E • GF-207 • 12/17/2019
Boiler Energy Input
BTU/Hr
0
0
385,000
(113 kW)
400,000
(117 kW)
540,000
(158 kW)
770,000
(226 kW)
1,160,000 (340 kW)
1,650,000 (484 kW)
2,386,000 (699 kW)
3,515,000 (1030 kW)
4,650,000 (1362 kW)
Energy Input in
Outlet
8"
(1.99 kPa)
6,000,000 (1758 kW)
8"
(1.99 kPa)
6,000,000 (1758 kW)
8"
(1.99 kPa)
5,860,000 (1717 kW)
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
% of Full
Capacity
0%
0%
6%
7%
9%
13%
19%
28%
40%
59%
78%
Oxygen
BTU/hr
(%O
2
5.40
5.40
5.45
DeRating
)
(% Full Fire)
0%
0%
2%
Page 43 of 95