SECTION 3 START SEQUENCE
3.4 Start/Stop Levels – Air/Fuel & Energy Input
The table below shows the relationship between the energy input and A/F Valve position.
TABLE 3-2: Air/Fuel Valve Position – NATURAL GAS
A/F VALVE
POSITION
(% OPEN)
25% (Stop Level)
30%
40%
50%
60%
70%
80%
90%
100%
ENERGY INPUT
(BTU/HR)
CFR 3000
CFR 1500
500,000
250,000
620,000
325,000
960,000
570,000
1,350,000
800,000
1,800,000
960,000
2,160,000
1,100,000
2,350,000
1,225,000
2,600,000
1,350,000
3,000,000
1,500,000
BOILER ENERGY INPUT
(% OF FULL CAPACITY)
CFR 3000
CFR 1500
17%
17%
21%
22%
32%
38%
45%
53%
60%
64%
72%
73%
78%
82%
87%
90%
100%
100%