6.2.1
Residual-current protective
device
Permanent connection
Plug-in connection
6.2

Making the electrical connection

Electrical installation work must be performed by a licensed electrician.
Comply with the local regulations of the electric utility.

Connecting to the electric mains

To connect the unit to the electrical supply mains, a connection line type
H07RN-F should be used.
The unit can be connected to a residual-current protective device. The
residual-current protective device must incorporate a residual-current
protective switch of type B (RCD Type B) in order to detect AC fault currents,
pulsating DC currents and continuous DC currents.
RCD switch type B circuit symbol
CAUTION
Risk of property damage and personal injury from improper installation
a) In the case of a permanent electrical connection, install an all-phase
disconnect switch before the unit.
Install an all-phase disconnect switch if the unit will be connected
permanently to the electric mains.
CAUTION
Risk of property damage and personal injury from improper installation
a) The plug-in connection must be readily accessible.
If the unit is connected with a plug to the power-supply mains, use plugs and
sockets according to IEC60309. The socket must be readily accessible so
that the unit can be disconnected from the electric mains at any time.
Connecting the unit
Making the electrical connection
6
23