4 Before installation
Tab.8
Type of flue system: C
Principle
(1) The material must also satisfy the material property requirements from the relevant chapter.
Tab.9
Type of flue system: C
Principle
(1)
AD-3001059-01
(1) See table for shaft or duct requirements.
(2) The material must also satisfy the material property requirements from the relevant chapter.
Tab.10
Minimum dimensions of shaft or duct C
Version (D)
Rigid 100 mm
Rigid 150 mm
Rigid 200 mm
Concentric 100/150 mm
Concentric 150/200 mm
Fig.7
Minimum dimensions of shaft or
duct C
93
D
Ø
4.5.2

Material

16
63
Description
This system is supplied by us without an air inlet and flue.
When selecting the material, please note the following:
Condensed water must flow back to the boiler.
The material must be resistant to the flue gas temperature of
this boiler.
Maximum permissible recirculation of 10%.
The air inlet and flue must not be placed on opposite walls.
Minimum permitted pressure difference between the air inlet
and the flue is -200 Pa (including -100 Pa wind pressure).
93
Description
Room-sealed version.
Air inlet and flue in shaft or duct:
Concentric.
Air supply from existing shaft or duct.
Flue gas discharge via the roof.
Air inlet is in the same pressure zone as the flue.
93
Without air supply
Ø 160 mm
Ø 200 mm
Ø 250 mm
Ø 170 mm
Ø 270 mm
D
AD-3000330-03
□ 160 x 160 mm
□ 200 x 200 mm
□ 250 x 250 mm
□ 170 x 170 mm
□ 270 x 270 mm
Important
The shaft must comply with the airtightness requirements of the
local regulations.
Important
Always clean shafts thoroughly when using flue liners and/or an
air supply connection.
It must be possible to inspect the flue liner.
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
Recommended manufactur­
ers
(1)
Use is only allowed when all
our requirements are met and
the description of this type of
flue system is respected.
Recommended manufactur­
ers
(2)
Connection material and roof
terminal:
Alukan
Burgerhout
Cox Geelen
Muelink & Grol
With air supply
Ø 170 mm
□ 160 x 160 mm
Ø 220 mm
□ 220 x 220 mm
Ø 280 mm
□ 280 x 280 mm
Ø 170 mm
□ 170 x 170 mm
Ø 270 mm
□ 270 x 270 mm
7837114 - v.01 - 10012023