Outlets; Material - REMEHA Quinta Ace Installation, User And Service Manual

Table of Contents

Advertisement

6 Installation
Tab.10
Shaft dimensions
Type
Version
C
Rigid
93
C
Flexible
93
C
Concentric
93
28
Diameter
Minimum dimensions of shaft or duct
Without air supply
Ø duct
100 mm
150 mm
150 mm
200 mm
200 mm
250 mm
100 mm
150 mm
150 mm
200 mm
200 mm
250 mm
100/150 mm
200 mm
150/220 mm
270 mm
6.5.2
Flue systems (roof feed-through and outside wall feed-through) must be
supplied by the following manufacturers:
Cox Geelen
Muelink & Grol
Ubbink
Important
Where regulations stipulate that a wire grille must be fitted, use a
suitable grille made from stainless steel.
Boiler-specific roof and outside wall feed-through kits are also available.
Note
Contact us for more information.
6.5.3
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers.
The materials used must comply with the prevailing regulations
and standards.
Tab.11
Design
(1)
Single-wall, rigid
Flexible
(1) The sealing must conform to pressure class 1
(2) With CE marking
□ duct
150 x 150 mm
200 x 200 mm
250 x 250 mm
150 x 150 mm
200 x 200 mm
250 x 250 mm
200 x 200 mm
270 x 270 mm

Outlets

Material

Flue gas outlet pipework materials
With air supply
Ø duct
□ duct
150 mm
150 x 150 mm
220 mm
220 x 220 mm
280 mm
280 x 280 mm
150 mm
150 x 150 mm
220 mm
220 x 220 mm
280 mm
280 x 280 mm
-
-
-
-
Material
(2)
Thick-walled, aluminium
Plastic T120
Stainless steel
Plastic T120
Stainless steel
7625116 - v.04 - 17012017