Fig.4
Minimum dimensions of shaft or
duct C
93
D
Ø
4.5.2

Material

Fig.5
Sample string
EN 14471 - T120 P1 W 1 O50 LI E U0
2
3
1
EN 1856-1 - T120 P1 W VxL40045 G(xx)
Tab.11
Overview of material properties
Version
Flue gas outlet
Material
Single-wall, rigid
Plastic
Stainless steel
Thick-walled,
aluminium
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
7684359 - v.11 - 13122021
D
AD-3000330-03
4
5
AD-3001120-01
Material properties
With CE marking
(1)
Temperature class T120 or
(2)
higher
Condensate class W (wet)
(2)
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
Important
The shaft must comply with the air density requirements of the
local regulations.
Important
Always clean shafts thoroughly when using lining pipes and/or
an air supply connection.
It must be possible to inspect the lining duct.
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
1 EN 14471 or EN 1856–1: The material is CE approved according
to this standard. For plastic this is EN 14471, For aluminium and
stainless steel this is EN 1856-1.
2 T120: The material has temperature class T120. A higher number
is also allowed, but not lower.
3 P1: The material falls into pressure class P1. H1 is also allowed.
4 W: The material is suitable for draining condensation water
(W='wet'). D is not allowed (D='dry').
5 E: The material falls into fire resistance class E. Class A to D are
also allowed, F is not allowed. Only applicable to plastic.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof terminal and common shared flue ducts.
The materials used must comply with the prevailing regulations
and standards.
Please contact us to discuss using flexible flue gas outlet
material.
Air supply
Material
Plastic
Stainless steel
Aluminium
4 Preparation of installation
Material properties
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)