6 Installation
Type
Principle
C
63(X)
(1) The material must also satisfy the material property requirements from the relevant chapter.
Fig.12
Sample string
EN 14471 - T120 P1 W 1 O50 LI E U0
2
1
3
EN 1856-1 - T120 P1 W VxL40045 G(xx)
Tab.13
Overview of material properties
Version
Flue gas outlet

Material

Single-wall, rigid
Plastic
Stainless steel
Thick-walled,
aluminium
(1) according to EN 14471
(2) according to EN 1856
(3) according to EN 13501-1
26
Description
This type of unit is supplied by the manufacturer
without a supply and discharge system.
6.5.2
Use the string on the flue gas outlet material to check whether it is suitable
for use on this appliance.
5
4
AD-3001120-01
Material properties
With CE marking
(1)
Temperature class T120 or
(2)
higher
Condensate class W (wet)
(2)
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)
Material
1 EN 14471 of EN 1856–1: The material is CE approved according to
this standard. For plastic this is EN 14471, For aluminium and
stainless steel this is EN 1856-1.
2 T120: The material has temperature class T120. A higher number
is also allowed, but not lower.
3 P1: The material falls into pressure class P1. H1 is also allowed.
4 W: The material is suitable for draining condensation water
(W='wet'). D is not allowed (D='dry').
5 E: The material falls into fire resistance class E. Class A to D are
also allowed, F is not allowed. Only applicable to plastic.
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers. This also
applies to roof feed-throughs and common channels.
The materials used must comply with the prevailing regulations
and standards.
Please contact us to discuss using flexible flue gas outlet mate­
rial.
Air supply
Material
Plastic
Stainless steel
Aluminium
Permitted manufacturers
(1)
When selecting the material,
please note the following:
Condensed water must flow
back to the appliance
The material must be resist­
ant to the flue gas tempera­
ture of this appliance.
Maximum permissible recir­
culation of 10%.
The air supply and the flue
gas outlet must not be placed
on opposite walls.
Minimum permitted pressure
difference between the air
supply and the flue gas outlet
is -200 Pa (including -100 Pa
wind pressure).
Material properties
With CE marking
Pressure class P1 or H1
Fire resistance class E or bet­
ter
(3)