 PID process adopts normalized input and output, that is, both the input and output range are between
-100%~+100%. The input scaling is related to feedback channel, sensor characteristics and analog input
setting. The output scaling takes the maximum frequency as 100% for frequency control.
There is a filtering section for the PID reference channel and feedback channel, for example, the filtering
time for AI1 is F6-03. These filtering sections have influence on the control performance and can be set
according to the actual needs.
 In some machines (such as centrifuges), the square root of the inlet pressure has a linear relationship with
the flowrate, therefore, the square root feedback can be used to control the flowrate.
 F7-03 is used to scale FU-13 and FU-14, making them match the real physical units. It has no influence
on the control.
F7-05
Setting
0.00~100.00
range
F7-06
Setting
0.01~100.00s
range
F7-07
Setting
0.01~10.00s
range
F7-08
Setting
0.00~100.00
range
F7-09
Setting
0.01~100.00s
range
F7-10
Setting
0.01~10.00s
range
F7-11
Setting
0: By digital input 36
range
3: |Arithmetic unit 2|
 Hope800 has two sets of PID parameters: PID parameter 1(F7-05, F7-06, F7-07) and PID parameter
2(F7-08, F7-09, F7-10). They can be switched mutually by the digital input 36. They can also be
94
AI1
1:
2: PFI
6:
AI2
10: Arithmetic unit 2
PID display coefficient
PID digital reference
Proportional gain 1
Integral time 1
Differential time 1
Proportional gain 2
Integral time 2
Differential time 2
PID parameter switching
3: AI1-AI2
AI1 -
7:
AI2
11:
Arithmetic unit
3
Default
Default
Default
Default
Default
Default
Default
Default
Default
1: According to operating
frequency
4: |Arithmetic unit 3|
4: AI1+AI2
8:
AI1+
AI2
12: Arithmetic unit 4
1.000
Change
0.0%
Change
0.20
Change
20.00s
Change
0.00s
Change
0.20
Change
20.00s
Change
0.00s
Change
0
Change
2: |Arithmetic unit 1|
5: |Arithmetic unit 4|
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents