motor decelerates. Afther the current drops the motor reaccelerates to the original operating frequency.
See diagram(b) below.
During deceleration, when Fb-16 is valid and the DC link voltage is greater than Fb-17, the deceleration
stops temporarily. After the DC link voltage drops to the normal level the motor continues to decelerate.
See diagram (c) below.
Output current
Overcurrent stall
point(accel)
Frequency
If stall holding time exceeds 1min during actual operation, the inverter will show "Er.Abb abnormal
shutdown failure", which can be shielded by selecting "2: valid with unlimited time".
Fb-18
DC link undervoltage action
0: Coast to a stop and report the undervoltage fault(Er.dcL)
1: Coast to a stop, and restart if the voltage resumes within the time set by Fb-20 or report the
undervoltage fault(Er.dcL) if undervoltage time exceeds the time set by Fb-20
Setting
2: Coast to a stop, and restart if CPU is still working and detects that the voltage resumes,
range
without reporting the undervoltage fault
3: Decelerate, and accelerate to the reference frequency if CPU is still working and detects
that the voltage resumes, without reporting the undervoltage fault.
Fb-19
DC link undervoltage point
Setting
370~480V, default 400V
range
Allowable time for momentary power
Fb-20
Setting
0.0~30.0s
range
Fb-21
Momentary power failure decel time
Setting
0.0~200.0s (if Fb-21=0.0, the current decel time is used)
range
The detection of momentary power failure is completed by detecting the DC link voltage. When DC link
voltage is less than Fb-19,
if Fb-18=0: The motor coasts to a stop, and the fault of DC link undervoltage is reported;
if Fb-18=1: The motor restarts if the voltage resumes within the time set by Fb-20(refer to Fb-25 for
start mode), or the undervoltage fault is reported if undervoltage time exceeds the time set by Fb-20;
if Fb-18=2: The motor restarts (refer to Fb-25 for start mode) if CPU is still working and detects that the
voltage resumes;
if Fb-18=3: The motor first decelerates according to the Fb-21 time or current decel time, then
accelerates to the reference frequency if the voltage resumes.
Overcurrent stall
point(constant
speed)
Time
Frequency
Time
(a)
failure
6 Parameter Description
Output current
Time
Time
(b)
Default
0
400V
Default
Default
0.1s
Default
0.0s
DC bus voltage
Overvoltage
stall point
Frequency
(c)
Change
×
×
Change
×
Change
×
Change
113
Time
Time