6 Parameter Description
21: Running in generating state. This signal is valid when the inverter is running in the generating
state.
22: Running at zero speed. This signal is valid when the motor speed is lower than F9-21.
23: Zero-servo finished. This signal is valid when the zero-servo position error is less than the
zero-servo ending value.
24: PLC operation. This signal is valid when the inverter is in the simple PLC operation mode.
25: PLC operation pause. This signal is valid when the digital input 23 is valid.
26: PLC stage finished. A 500ms pulse is sent out each time a stage of PLC operation is completed.
27: PLC cycle finished. A 500ms pulse is sent out each time a cycle of PLC operation is completed.
28~29: PC digitals 1 & 2. Can be used by the programmable unit. Refer to page 116.
30: Wobble frequency upper/lower limit. Refer to Section 6.10.
31, 32, 69: Setpoint count reach, designated count 1 & 2 reach. Refer to Section 6.10.
33: Meter-counter setpoint length reach. Refer to section 6.10.
34~39: X1~X6(after positive & negative logic). These are digital input signals which have undergone
positive & negative logic operation and anti-jittering treatment. They can be used by the programmable unit.
40~44: X7~X11(expansion terminals). These are expansion digital input signals which have undergone
anti-jittering treatment and can be used by the programmable unit.
45, 46: FWD and REV (after positive & negative logic). These are digital input signals which have
undergone positive & negative logic operation and anti-jittering treatment. They can be used by the
programmable unit.
47, 48: Comparator 1 & 2 outputs. Can be used by the programmable unit.
49~52, 70, 71: Logic unit 1~6 outputs. Can be used by the programmable unit.
53~56: Timer 1~4 outputs. Can be used by the programmable unit.
Encoder A & B channels. Can be used as the high-speed input of the counter and
57, 58:
meter-counter.
59: PFI terminal status. Can be used as the high-speed input of the counter and meter-counter.
60: Virtual revolution-counting pulse. It is a pulse signal with a duty ratio of 50%. It can be connected
to the counter for the calculation of the winding diameter in winding control.
61~68: PLC mode 0~7 indication. Used to indicate the serial number of current PLC mode
72: Expected service life of air blower reached. Refer to page 120.
73: Process PID sleeping. Refer to page 120.
F5-04
Y output logic(positive & negative)
Tens digit: Y2
Setting
0: Positive logic, valid when closed and invalid when open
range
1: Negative logic, valid when open and invalid when closed
 This parameter can negate the Y1 and Y2 signals and output them.
F5-05
Frequency reach detection band
86
Units digit: Y1
Default
00
Default
2.50Hz
Change
×
Change